Theory: | Electromagnetic Relay |
---|---|
Usage: | General Purpose |
Phase: | 3 |
Samples: |
---|
Customization: |
---|
Shipping Cost:
Estimated freight per unit. |
about shipping cost and estimated delivery time. |
---|
Payment Method: | |
---|---|
Initial Payment Full Payment |
Currency: | US$ |
---|
Return&refunds: | You can apply for a refund up to 30 days after receipt of the products. |
---|
Suppliers with verified business licenses
Protection against over-current,phase-out and locked-rotor
The startup delay or operation delay can be set separately
Adopt relay suitable for vibration and short circuit
Wide voltage range setting
Confirm operation display and running current(LED)
Manual(immediate)/automatic reset
Fault protection function
Ultra low power consumption
Technical Parameters:
Product model
|
Two-phase
|
AORD-06/2
|
AORD-30/2
|
AORD-60/2
|
AORD-120/2
|
|
Three-phase
|
AORD-06/3
|
AORD-30/3
|
AORD-60/3
|
AORD-120/3
|
||
Setting current(A)
|
1~6A
|
5~30A
|
5~60A
|
10~120A
|
||
|
Starting D-Time
|
0.2~60 sec
|
||||
Operation O-Time
|
0.2~12 sec
|
|||||
Reset
|
Manual/Electric Reset
|
|||||
Operating Time Spec
|
Constant time-lag
|
|||||
|
Current
|
±5%
|
||||
Time
|
±5%
|
|||||
Operating Voltage
|
Voltage range
|
230V
|
AC 90~260V
|
|||
400V
|
AC 180~460V
|
|||||
Frequency
|
50/60Hz
|
|||||
Auxiliary Contactor
|
Contact
|
1-SPDT(1C)
|
||||
Capacity
|
5A/250VAC Resistive
|
|||||
Insulation
|
Between Case&Circuit
|
500VDC/100MQ
|
||||
|
Between Case&Circuit
|
2.0kV,50/60Hz,1min
|
||||
Between contacts
|
1.0kV,50/60Hz,1min
|
|||||
Between circuit
|
2.0kV,50/60Hz,1min
|
|||||
Environment
|
|
Storage
|
-30~80ºC
|
|||
Operation
|
-20~60ºC
|
|||||
Humidity
|
30~85% RH Not-condensate
|
|||||
Mounting
|
35mm DIN-Rail / Panel
|