Customization: | Available |
---|---|
Electricity Type: | AC |
Number of Pole: | 3 |
Still deciding? Get samples of US$ 69/Piece
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
SMC-type contactor is mainly used in the electric system with AC 50Hz/60Hz,the maximum voltage 660 V, and the maximum current 800A.lt is used for long distance swich-on and of circuit and frequently-starting motor.
lf properly combined with thermal overload relay device, it can work as starter of motor to prevent overload or open-phase. Series of such contactors can be equipped with toy-brick type auxiliary heads, air time-delay heads and interlocking device to act as time-delay contactor,reversing contactor, switching contactor and star-delta starter.Technical Parameters:
Type |
SMC-110 |
SMC-130 |
SMC-150 |
|||||||
Rated Power kW/HP(AC-3) IEC60947-4-1 |
200-240V |
30/40 |
37/50 |
45/60 |
||||||
380-440V |
55/75 |
60/80 |
75/100 |
|||||||
500-550V |
55/75 |
60/80 |
90/120 |
|||||||
660-690V |
55/75 |
60/80 |
90/120 |
|||||||
Rated Current A(AC-3) |
200-240V |
110 |
130 |
150 |
||||||
380-440V |
110 |
130 |
150 |
|||||||
500-550V |
85 |
90 |
140 |
|||||||
660-690V |
65 |
70 |
100 |
|||||||
Conventional Thermal Current Ith:(A) |
160 |
160 |
210 |
|||||||
Rated Insulated Voltage Ui:(V) |
690 |
|||||||||
Auxiliary
Contact
AC-15 |
Contact Arrangement
|
Standard |
2NO+2NC |
|||||||
Special |
Optional |
|||||||||
Rated Current A(AC-15)
IEC60947-5-1
GB14048.5
|
200-240V |
1.6 |
||||||||
380-440V |
0.95 |
|||||||||
Conventional Thermal Current Ith:(A)
|
16 | |||||||||
Mechanical Life(Million Times) | 6 |
Characteristics:
Auxiliary electrified contact block is used,convenient for installation.
Contactor and thermal relay can be connected directly,without any other fittings.
Install by using screws or directly install at the standard guide track of 35mm.
lt is easy to replace coil for using drawout type coil structure and unnecessary to dismantle contactor.
Various accessories.
Q1. What's the payment term?